
Print test
184 Multiple choice questions
- ≥2:12
- allows for drying of roof material.
- Determine the degree of immediacy, and report to the appropriate parties.
- False
- Cosmetic
- Recommend installing a metal dryer duct vented to the exterior.
- Type "B" UL approved
- 40
- Moisture
- V-3 rule
- wood siding
- girder
- 8.33
- New, sharp cracks
- As large as the relief valve outlet.
- 15
- dried out
- Report on the condition, and inform the homeowner that an electrician should review.
- Three
- Check to see if the bedroom doors are undercut at the bottom
- highly expansive clay soils.
- A pin hole in the heat exchanger
- 20
- An office or bedroom
- empty space so that it doesn't overheat anything
- A missing temperature and pressure relief valve on a hot water heater
- Nominal 1- or 2-inch-thick members connecting opposite roof rafters. They serve to stiffen the roof structure.
- True
- that a sub-panel is present
- Approved brace or box.
- Upon approval of a structural engineer
- ≥ 6"/10'
- the rusting of steel lintels is causing the expansion
- A clear air channel between the roof boards and the insulation.
- Is below the sewer line.
- not be notched.
- Mat foundation slab
- The trusses are no longer structurally sound, and the best method of correction should be determined by qualified engineer.
- too close to the openable window.
- You are not allowed to discuss your findings with them.
- is secured to the plumbing "closet flange" by two closet bolts.
- lateral forces.
- a minimum of 3 feet above the roofline and 2 feet higher than any other obstruction within 10 feet
- ≥8% of floor area
- CO detector
- Nails or screws in the floor
- 16 inches.
- Three light testers will not detect multiple wiring problems
- 15
- Lead particles freed in fine dust or vapors do not settle into carpet fibers
- 1
- Moved
- Sensible and latent heat
- False
- Check to see if the bedroom doors are undercut at the bottom.
- White-rot fungi
- improperly installed materials that do not allow for expansion.
- Could cause damage to the surface and recommend removal.
- Three feet above roof penetration and two feet above the highest point within 10 feet.
- Conclusion
- Floor joist
- Where
there is not a vapor retarder applied to the floor of the attic, but
there is insulation applied to the underside of the roof deck.
- The yard
- Gas water heater.
- The
full condensate pan tripped a condensate overflow switch. The unit
turned off in order to ensure that condensate did not spill.
- 3..... 2..... 10
- 30
- True
- Not exist under any condition.
- unit may not be venting properly
- Anywhere from 1/8:1 to 1/2:1
- Approved brace or box
- risers
- Normal plastic shrinkage.
- Egress windows must have a clear height of at least 16 inches.
- channel
- Correct answer: Pipe set in gravel running continuously along the exterior of a building's foundation footings.
- They increase the shock likelihood at connected equipment.
- that the notch exceeds maximum allowable depth and needs proper repair
- Waste line that also functions as a vent.
- Insufficient attic insulation.
- Risk of small children falling in the pool.
- 3/4 inch.
- building settlement
- Refuse since it is a violation of ethical practice.
- An interior wall that is not connected to a loft or the second story floor joists
- Condensation.
- True
- Inspect the wood behind the siding by removing a piece.
- Insufficient attic insulation
- block sewer gas.
- valley
- The fuse box
- House is in sound structural condition.
- Looks like stucco but lacks a wire mesh.
- undersized
- Use joist hangers nailed to both the joist and the ledger.
- 3
- Slowing the draft that accelerates at the top of the flue.
- 9 inches
- a minimum of 3 feet above the roof line and 2 feet higher than any other obstruction within 10 feet
- a proper installation
- Too much water is added.
- Use a voltage "sniffer."
- soapy water.
- All of the above
- You select one electrical outlet to test in each room of the structure.
- Coupled together.
- studs
- False
- closets of bedrooms or bathrooms.
- An electric heater
- The bathroom door sticks, which may have caused the drywall crack above it.
- No bond courses are seen.
- >5 ft or into a drain pipe
- Concaved.
- Water vapor has a tendency to disperse itself equally in the available air.
- There must be a ground fault circuit interrupter.
- It should be more than 12 inches thick and extend six inches beyond the fireplace on all sides.
- steam heating
- secure the roof framing to prevent spreading outward.
- 120°F.
- 36 inches.
- provides lateral support.
- tile or slate
- False
- a leaking check valve.
- Consideration
- There does not appear to be any fire barrier between the garage and living space as currently required.
- At least 5.7 sq. ft
- Mixing valve
- 6 feet.
- 40 and 80 psi
- properly sized lag bolts every 16 inches.
- Open windows, shut down systems, and advise immediate evaluation by an HVAC contractor.
- cement, lime, and sand
- This is allowed only if the additional load has been verified as acceptable by a certified engineer.
- Sloped away to provide proper drainage.
- Balloon framing.
- A 1/2 inch wide wall/floor separation
- Heat exchanger.
- Gas piping.
- 15-20 ° F.
- General liability and homeowners' coverage
- True
- 18 inches.
- Prevent movement.
- Potential safety issue
- ≥ 3"
- will probably have reduced water volume and pressure
- water heaters
- 30
- minimum of 2 inches
- R30.
- There must be a ground fault circuit interrupter.
- Surety
- At least 8"
- Suggest obtaining the services of a pest control operator.
- Use kick-out flashing into the gutter.
- 100 feet horizontally
- 3 inches
- 1/4 inch to 1/2 inch per foot.
- the pressure tank is probably water logged.
- mechanical vent
- 125
- Looks like stucco but lacks a wire mesh
- water-logged expansion tank
- All of the above
- Floor joist
- Shut-off valves.
- At the corners of the installation, such as around windows
- shut gas off.
- 6" fiberglass batt insulation
- Post and beam construction, balloon framing, platform framing, ICF construction
- Over hydrated concrete.
- Both A and B
- The inspector should recommend this situation be referred to a structural engineer.
- 3/12
- True
- Exhaust spillage.
- If you inspect appliances, tell your client that you will check them out.
- The term for attaching two wires to a single fuse or breaker terminal
- May require expensive replacement.
- Balloon