
Print test
214 Multiple choice questions
- When
all conductors are the same size, Table _______ can be used to
determine the number of conductors permitted in the outlet box, or
determine the size outlet box required for the given number of
conductors
- Depth
of Box and Conduit body sizing: When conductors enter an enclosure
opposite a removable cover, such as the back of a pull box or conduit
body, the distance from where the conductors enter to the removable
cover should be calculated according to Table _____, one wire per
terminal.
- (220)
The connected load to which the demand factors of Table 220-84 apply
shall include 3 volt-amperes per _____ for general lighting and
general-use receptacles.
- How many #10 THHN are permitted in a 4 x 1 ½ square box?
- Equipment
enclosed in a case or cabinet that is provided with a means of sealing
or locking so that live parts cannot be made accessible without opening
the enclosure is said to be _______.
- (240)
Fuseholders of the Edison-base type shall be installed only where they
are made to accept _____ fuses by the use of adapters.
- (230)
The _____ clearances for all service drop conductors shall be based on a
conductor temperature of 60 degrees F, no wind; with final unloaded sag
in the wire, conductor, or cable.
- A unit of an electrical system, which is intended to carry, but not utilize electrical energy. Is a______.
- (240)
Flexible cords approved for use with listed appliances or portable
lamps shall be considered as protected by a 20 ampere circuit breaker if
they are ____.
- (210)All
125 volt, single phase 15 and 20 ampere receptacles installed in
bathrooms of guest rooms in hotels/motels, dwelling units, and office
buildings shall have ____________for personel.
- The minimum headroom of working spaces about motor control centers shall be _____.
- Box Fill Requirements: Each conductor that runs through the box is considered as _____ conductor.
- Box
Fill Requirements: Each yoke or strap containing one or more devices or
equipment is considered as ____ conductors, based on the ______
conductor that terminates on the yoke.
- (240)
Overcurrent protection devices are not permitted to be located where
exposed to physical damage; near easily ignitable materials, such as
clothes closets; in bathrooms of dwelling units.(True/False)
- A
_____ switch is a manually operated device used in conjunction with a
transfer switch to provide a means of directly connecting load
conductors to a power source and of disconnecting the transfer switch.
- A
qualifying term indicating that there is a purposely introduced delay
in the tripping action of the circuit breaker, which delay decreases as
the magnitude of the current increases, is defined by the Code as a
_____ circuit breaker.
- The
actual area of conductor fill is dependent on the raceway size and the
number of conductors installed. If there are three or more conductors
installed in a raceway, the total area of conductor fill is limited to
_____ percent.
- What is the area in square inches for a No. 10 THW?
- (210)At
least _____ wall switch-controlled lighting outlet(s) shall be
installed in every dwelling unit habitable room and bathroom.
- The
necessary equipment, usually a circuit breaker or switch and fuse and
their accessories, intended to constitute the main control and cutoff of
the supply is referred to as _____.
- A(n) ______ is a point on a wiring system where current is taken to supply equipment that uses electricity.
- (210)When
breaks occur in dwelling unit kitchen countertop spaces for ranges,
refrigerators, sinks, etc., each countertop surface is considered a
separate counter space for determining receptacle placement.(True/False)
- Openings
in ventilated dry-type _____ or similar openings in other equipment
over 600 volts shall be designated so that foreign objects inserted
through these openings will be deflected from energized parts.
- (230)
Service conductors shall be connected to the disconnecting means by
pressure connectors, clamps, or other approved means(True/False)
- (Article
90) The Code applies to the installation of electrical conductors and
equipment within or on public and private buildings, of outside
conductors and equipment on the premises, and of optical fiber cable.
(True,False)
- To
guard live parts over 50 volts but less than 600 volts, the equipment
can be isolated in a room accessible to qualified persons only, located
on a balcony, or elevated 8 feet or more above the floor (True/False)
- Pull
Box Sizing, Vertical Dimension: A pull box contains two 4 inch raceways
on the left and two 2 inch raceways on the top. What is the vertical
dimension of the box?
- Box
Fill Requirements: One or more internal cable clamps are considered as
_____ conductors based on the ____ conductor that enters the box
- A two-family dwelling unit, such as a duplex apartment, is considered a single family dwelling. (True/False)
- (240) A current transformer and overcurrent relay shall be considered equivalent to an overcurrent trip unit(True/False)
- It is permitted to omit one equipment grounding conductor and not more than ______ that enter a box from a fixture canopy.
- Compliance with the provisions of the Code will result in _____. (Article 90)
- A
3 inch schedule 40 PVC raceway contains seven No. 1 RHW conductors
without outer cover. How many No. 2 THW conductors may be installed in
this raceway with the existing conductors?
- (230)
When ground-fault protection is provided for the ____ disconnecting
means and interconnection is made with another supply system by a
transfer device, means or devices may be needed to ensure proper
ground-fault sensing by the ground-fault protection equipment.
- A
thermal protector may consist of one or more heat-sensing element
integral with the motor or motor-compressor and an external control
device.(True/False)
- Pull
Box Sizing, Distance between Raceways: A junction box contains two 3
inch raceways on the left side and one 3 inch raceway on the right side.
The conductors from one of the 3 inch raceways on the left are pulled
through the 3 inch raceway on the right wall. The other 3 inch raceways
conductors are pulled through ta raceway at the bottom of the pull box.
What is the minimum distance between the two three inch raceways that
contain the same conductors (314-28a-2)?
- (210)For
a one-family dwelling at least one receptacle outlet is required in
each basement, attached garage, or detached garage with electric
power.(True/False)
- Warning signs for over 600 volts shall read "Warning - High Voltage - Keep Out". (True/False)
- (230)
To supply power to a single-phase water heater, the size of the
underground service lateral conductors shall not be smaller than _____.
- (250)
Supplementary grounding electrocces can supplement the equipment
grounding conductor, but they cannot be used as the sole equipment
grounding conductor.(True/False)
- For
a circuit to be considered a multiwire branch circuit, it must have two
or more ungrounded conductors with a potential difference between them,
a grounded conductor having equal potential difference between it and
each ungrounded conductor of the circuit, and a grounded conductor
connected to the neutral (grounded) conductor of the system.(True/False)
- (240)
No overcurrent protection device shall be connected in series with any
conductor that is intentionally grounded, except where the overcurrent
protection device opens all conductors of the circuit including the
_____ conductor, and is so designed that no pole can operate
independently.
- A
round 3 x 1 ½ box has a volume of 6 cubic inches and has factory
internal cable clamps. Can this pancake box be used with a lighting
fixture that has a domed canopy? Thee branch circuit wiring is 14/2 NM
sheath cable and a paddle fan has three fixture wires and one ground
wire all smaller than No. 14
- A
junction box contains two 2 inch raceways on the left side and two 2
inch raceways on the top. What is the distance from the bottom to the
top wall?
- Design
B, C, D, or E motors shall be wired with conductors having an
insulation rating of at least _____ degrees C, and the conductor shall
be sized based on the 75 degree C ampacity as listed in Table
310-15(B)(16) (formerly 310-16)
- An
insulated grounded conductor of No. ____ or smaller shall be identified
by a continuous white or natural gray outer finish along its entire
length.
- (230) The service disconnecting means shall plainly indicate whether it is in the _______ position.
- (230)
Overhead service conductors to a building shall maintain a vertical
clearance of 10 feet above platforms, projections, or surfaces from
which they might be reached. This vertical clearance shall extend _____
feet measured horizontally from the platform, projections, or surfaces
from which they might be reached.
- (220)
When sizing a feeder, the appliance loads in dwelling units can apply a
demand factor of 75 percent of nameplate ratings for ____ or more
appliances fastened in place on the same feeder.
- Ventilated
heating or cooling equipment (including ducts) that service the
electrical room or space cannot be installed in the dedicated space
above a panelboard or switchboard. (True/False)
- A
junction box contains two 2 inch raceways on the left side and two 2
inch raceways on the top. What is the distance from the left to the
right wall?
- (225) Lamps for outdoor lighting shall be below all _____, transformers or other electrical utilization equipment.
- (220) When a calculation results in a fraction of ampere of ____ or more, we "round up" to the next ampere.
- What
size outlet box is required for 14/3 type NM cable (with ground) that
terminates on a switch, with 14/2 NM cable that terminates on a
receptacle, if the box has internal cable clamps factory installed?
- (210)At
least one lighting outlet controlled by a wall switch, or containing a
switch, located at the point of entry to the attic, under floor space,
utility room, and basement shall be installed where these spaces are
used for storage or contain equipment requiring servicing.(True/False)
- (250)
When a building has two or more elecrodes for different services, the
separate electrodes must be ______. This shall be considered as a single
electrode in this sense.
- (230) A building or structure shall be supplied by a maximum of _____ services.
- Pull Boxes, Junction Boxes and Conduit Bodies must be sized according to Section _____
- Pull
Box Sizing, Horizontal Dimension: A pull box contains two 4 inch
raceways on the left and two 2 inch raceways on the top. What is the
horizontal dimension of the box?
- A
device or group of devices that serves to govern in some predetermined
manner the electric power delivered to the apparatus to which it is
connected is a ________
- What is the area in square inches for a No. 12 RHH (with outer cover)?
- A
junction box contains two 2 ½ inch raceways on the left side and one 2 ½
inch raceway on the right side. The conductors from one 2 ½ inch
raceway are pulled through the raceway on the righ wall. The other 2 ½
inch raceway conductors (on the side) are pulled through a 2 ½ inch
raceway at the bottom of the pull box. What is the distance from the
left wall to the right wall?
- A
value assigned to a circuit or system for the purpose of conveniently
designating its voltage class such as 120/240 volts is called
______voltage.
- Understanding
Chapter 9 Tables: When a raceway does not exceed 24 inches, the raceway
is permitted to be filled to _____ of its cross-sectional area.
- (210)In
a dwelling unit, every habitable room, including hallways and stairways
and bathrooms shall have a switch-controlled lighting
outlet.(True/False)
- (230)
Branch circuit and feeder conductors shall not be installed in the same
raceway or cable with service conductors.(True/False)
- A
system or circuit conductor that is intentionally grounded is a(n)_____
This conductor is often called a neutral conductor in the field, and is
identified with the color white or gray.
- The highest current at rated voltage that a device is intended to interrupt under standard test conditions is the ______.
- (230)
Circuits used only for the operation of fire alarm, other protective
signaling systems, or the supply to fire pump equipment shall be
permitted to be connected on the _____ of the service overcurrent
protection device where separately provided with overcurrent protection.
- (220)
The demand factors listed in Table 220-42 shall not be applied in
determining the number of _____ for general illumination.
- An
apparatus enclosed in a case that is capable of withstanding an
explosion of specified gas or vapor that may occur within it, and of
preventing the ignition of a specified gas or vapor surrounding the
enclosure by sparks, flashes, or explosion of the gas or vapor within,
and that operates at such an external temperature that a surrounding
flammable atmosphere will not be ignited is defined as _____.
- (250) _____on equipment to be grounded shall be removed from contact surfaces to ensure good electrical continuity.
- (240) Breakers and fuses can be used in parallel when factory assembled in parallel or listed as a unit.(True/False)
- (210)The recommended maximum total voltage drop on both the feeders and banch circuits is _____ percent.
- (250)
Where service-entrance conductors are installed in parallel, the
grounded conductor in each raceway can be sized, based on the size of
the ungrounded service-entrance (phase) conductor in the raceway, but
not smaller than _____.
- Box
Fill Requirements: One or more fixture studs or hickeys within the box
are considered as ____ conductors based on the _____ conductor that
enters the box.
- (240) Cartridge fuses and fuseholders shall be classified according to _____ranges.
- What size rigid metal nipple is required for three No. 4/0 THHN, one No. 1/0 THHN and one No. 4 THHN?
- (230) Each ______ service conductor shall have overload protection.
- Can
a round 4 x ½ box marked as 8 cubic inches with manufactured cable
clamps supplied with 14/2 NM be used with a fixture that has two No. 18
TFN and a canopy cover?
- (230) Where individual open conductors are not exposed to the weather, the conductors shall be mounted on _____knobs.
- (230)
As used in Section 230-95, the rating of the service disconnecting
means is considered to be the rating of the largest _____ that can be
installed or the highest continuous current trip setting for the actual
overcurrent protection device installed in a circuit breaker is rated or
can be adjusted.
- (230) Service heads must be located _____.
- Pull
Box Sizing, Horizontal Dimension: A junction box contains two 3 inch
raceways on the left side and one 3 inch raceway on the right side. The
conductors from one of the 3 inch raceways on the left are pulled
through the 3 inch raceway on the right wall. The other 3 inch raceways
conductors are pulled through ta raceway at the bottom of the pull box.
What is the horizontal dimension of this box?
- (225)
Communications conductors shall be mounted not less than ____ inches
below power conductors rated over 300 volts supported on poles.
- Existing
Metal Raceways: An existing Rigid metal nipple contains four No. 10
THHN and one No. 10 (bare stranded) ground wire in a 1/2 inch metal
conduit. How many additional No. 10 THHN can be installed?
- (210)The
24 inch dimension required in a dwelling unit countertop is measured
along the wall line or center line, and the intent is that there be a
receptacle outlet for every _____linear feet or fraction thereof of
counter length.
- Pull
Box Sizing, Distance between Raceways: A pull box contains two 4 inch
raceways on the left and two 2 inch raceways on the top. What is the
minimum distance between the two 4 inch raceways that contain the same
conductors?
- If
a 250kcmil wire is run through a 3 inch raceway entry in the wall
opposite to a removable cover, the distance from that cover must not be
less than _______.
- Connection
of conductors to terminal parts shall ensure a thoroughly good
connection without damaging the conductors and shall be made by means of
solder lugs, pressure connectors, splices to flexible leads.
(True/False)
- (240)
Overcurrent protection for conductors and equipment is provided to
______ the circuit if the current reaches a value that will cause an
excessive or dangerous temperature in conductors or conductor
insulation.
- (230)
Individual open conductors and cables other than service-entrance
cables shall not be installed within _____ feet of grade level or where
exposed to physical damage.
- Identification
of the grounded conductor terminal on a device shall be by a metal or
metal coating substantially white in color or the word ______ located
adjacent to the identified terminal.
- How
many No. 14 THHN conductors can be pulled through a 4 x 1 ½ square box
with a plaster ring of 3.6 cubic inches? The box contains two duplex
receptacles, five No. 14 THHN and two grounding conductors.
- An
outlet intended for the direct connection of a lampholder, a lighting
fixture, or a pendant cord terminating in a lampholder is a(n) _____.
- (230)
Underground Service-entrance conductors are required to be insulated
except when they are bare copper installed in a raceway, or bare copper
and part of the cable assembly identified for underground
use.(True/False)
- The
working space in front of the electric equipment shall not be less tha
_____ inches wide or the width of the equipment, whichever is greater.
- (250)
Conductive materials enclosing electrical conductors or equipment are
grounded to limit the voltage to ground and are bonded to facilitate the
operation of overcurrent protection devices under ground-fault
conditions.(True/False)
- (225) Outside branch circuits and feeder conductors shall have a vertical clearance of _____ feet from the surface of a roof.
- (230) Overhead sevice drop conductors shall have a horizontal clearance of _____ feet from a pool.(680.8)
- (210)Receptacles
installed behind a bed in the guest rooms in hotels and motels shall be
located so as to prevent the bed from contacting an attachment plug, or
the receptacle shall be provided with a suitable guard.(True/False)
- Box
Fill Requirements: Each conductor that originates outside the box and
terminates or is spliced within the box is considered as ____ conductor.
- Pull
Box Sizing, Vertical Dimension: A junction box contains two 3 inch
raceways on the left side and one 3 inch raceway on the right side. The
conductors from one of the 3 inch raceways on the left are pulled
through the 3 inch raceway on the right wall. The other 3 inch raceways
conductors are pulled through ta raceway at the bottom of the pull box.
What is the vertical dimension of this box?
- (225)
Where buildings exceed three stories, overhead lines shall be arranged
so that a clear space at least 6 feet wide will be left either adjacent
to the buildings or beginning not over 8 feet from them to facilitate
the _____ when necessary for fire fighting.
- (210)A
dedicated 20-ampere circuit is permitted to supply power to a dwelling
unit bathroom for receptacle outlet(s) and other equipment within the
same bathroom.(True/False)
- (225) Conductors for ____ lighting shall be of the rubber-covered or thermoplastic type.
- (210)The
total rating of utilization equipment fastened in place shall not
exceed _____ percent of the branch circuit ampere rating, where the
circuit supplies receptacles for cord-and-plug connected equipment.
- Understanding
Chapter 9 Tables: When all the conductors are the same size and
insulation, the number of conductors permitted in a raceway can be
determined simply by looking at the Tables in ______.
- When
different wiring systems are in the same raceway or enclosure, the
grounded conductor of one system can be white and the grounded conductor
of the other system can be gray (True/False)
- (240)
Where an orderly shut down is required to minimize hazard() to
personnel and equipment, a system of coordination based on two
conditions shall be permitted. Those two conditions are
(10______short-circuit protection, and (2) ______ indication based on
monitoring systems or devices.
- (220)
For other than dwelling units, the feeder and service load calculation
for track lighting is to be determined at 150 volt-amperes for every
____ feet of track installed.
- (220) The feeder demand load for four 6 kw cooktops is _____ kW.
- What is the area in square inches of a No. 8 bare solid?
- (215)The
feeder conductor ampacity shall not be less than that of the
service-entrance conductors where the feeder conductors carry the total
load supplied by service-entrance conductors with an ampacity of ____
amperes or less.
- (210)Multiwire branch circuits shall supply only line to _____ loads
- Box
Fill Requirements: Wirenuts, cable connectors, raceway fittings and
conductors that originate and terminate within the outlet box (such as
equipment bonding jumpers and pigtails) are considered _____ conductor .
- Equipment
intended to break current at other than fault levels shall have an
interrupting rating at system voltage sufficient for the current that
must be interrupted.(True/False)
- The
2011 NEC defined ______ as all conductors between a source of power
from a battery, a solar voltaic system, generator, transformer, or
converter windings, and the final branch circuit overcurrent protections
device(s).
- (215)Where
a feeder supplies _____ in which equipment grounding conductors are
required, the feeder shall include or provide a grounding means to which
the equipment grounding conductors of branch circuits shall be
connected.
- (Article
90)Installations of communications equipment under the exclusive
control of communications utilities located outdoors or in building
spaces used exclusively for such installations ______ covered by the
Code.
- (220)
For each farm building or load supplied by _____ or more branch
circuits, the load for feeders, service-entrance conductors, and service
equipment shall be computed in accordance with demand factors not less
than indicated in Table 220-102.
- (240)
Plug fuses of 15 amperes and lower ratings shall be identified by a
_____ configuration of the window, cap, or other prominent part to
distinguish them from fuses of higher ampere ratings.
- (225)
Overhead branch circuit and feeder conductors shall not be installed
_____ openings through which materials may be moved, such as openings in
farm and commercial buildings, and hall not be installed where they
will obstruct entrance to these building openings.
- (Article 100) A junction box above a suspended ceiling that has removable panels is considered to be _______.
- Understanding
Chapter 9 Tables: When equipment grounding conductors are installed in a
raceway, the actual area of the conductor must be used when calculating
raceway fill. T/F
- (220)
The maximum unbalanced feeder load for household electric dryers shall
be calculated at ____ percent of the demad load as determined by Table
220-54.
- (250)
A grounding electrode is required if a building or structure is
supplied y a feeder, or by more than one branch circuit.(true/False)
- (210)Receptacle
outlets in a dwelling unit must be installed within _____ inches of the
outside edge of each basin and the receptacle must be located on a wall
that is adjacent to the basin location.
- When
determining the number of conductors in a box fill two No. 18 fixture
wires, one 14/3 nonmetallic sheathed cable with ground, one duplex
switch, and two cable clamps would count as ______ conductors.
- ____ branch circuits supply energy to one or more outlets to which appliances are to be connected.
- (230)
The requirement for maintaining a 3 foot vertical clearance from the
edge of the oof shall not apply to the final conductor span where the
service drop is attached to ______.
- Concrete, brick, or tile walls shall be considered as _____, as it applies to working space requirements.
- (250)
An additional electrode shall suppleent a metal underground water pipe.
Where the supplemental electrode is a made electrode as in Section
250-83(c) or (d), that portion of the bonding jumper that is the sole
connections to the supplemental grounding electrode shall not be
required to be larger than _____ wire.
- (Article
90) Plans and specification that provide ample space in raceways, spare
raceways, and additional spaces will allow for future increases in the
use of electricity. Distribution centers located in readily accessible
locations will provide convenience and safety of operation. (True/False)
- (220) Feeder conductors for new restaurants shall not be required to be of ______ ampacity than the service-entrance conductors.
- (240) Where used as switches in 120-volt and 277-volt fluorescent lighting circuits, circuit breakers shall be marked ______.
- (225) If festoon lighting exceeds a span of ____ feet, messenger wires shall support the conductors.
- (240) Markings on circuit breakers required by the Code shall be permitted to be made visible by removal of a _____ or cover.
- Entrances
to rooms and other guarded locations containing exposed live parts
shall be marked with conspicuous ____ forbidding unqualified persons to
enter.
- (Article
100) According to the Code, automatic is self-acting, operating by its
own mechanism when actuated by some impersonal influence such as change
in current strength, mechanical configuration, temperature. (True/False)
- So constructed that dust will not enter the enclosing case under specified test conditions is known as _____.
- Article
200 contains the requirements for the identification of terminals,
grounded conductors in premises wiring systems, identification of
grounded conductors. (True/False)
- Determine
the minimum cubic inches required for two No. 10 TW passing through a
box, four No. 14 THHN terminating, two No. 12 TW terminating to a
receptacle, and one No. 12 equipment bonding jumper from the receptacle
to the box.
- If
we have a 2 inch rigid metal conduit and we want to install three THHN
aluminum compact conductors, what is the largest aluminum compact
conductor permitted to be installed?
- (210)Grade-level
portions of ________and _______ accessory buildings used for storage or
work areas shall have ground-fault ciruit interrupter protection for
all 15 and 20 ampere, 125 volt receptacles.
- (240)
Fuseholders for cartridge fuses shall be so esigned that it is
difficult to put a fuse of any given class into a fuseholder that is
designed for a _____lower, or _____ higher, than that of the class to
which the fuse belongs.
- (220)
Feeder and service-entrance conductors with demand load determined by
the use of 220.80 shall be permitted to have the ____ load determined by
Section 220-61.
- Table 314-16 does not take in to consideration the volume of _____.
- (210)In
dwelling units, when determining the spacing of general use
receptacles, ____ on exterior walls are not considered wall space.
- Depth
of Pull or Junction Box: A 24" x 24" pull box has two 2 inch conduits
that enter the back of the box with No. 4/0 conductors. What is the
minimum depth of the box?
- How many #12 RHH (with outer cover) can be installed in 1" IMC raceway?
- (230)
Service entrance conductors can be spliced or tapped by clamped or
bolted connections at any time as long as the free ends of conductors
are covered with an insulation that is equivalent to that of the
conductors or with an insulating device identified for the purpose
(Sections 110-14); wire connectors or other splicing means installed on
conductors that are buried in the earth shall be listed for direct
burial [section 300-5e]; or No splice is made in the raceway [Section
300-13](True/False)
- (230)
Where the service overcurrent devices are locked or sealed, or not
readily accessible to the _____, the branch circuit overcurrent devices
shall be located in a readily accessible location.
- A
system intended to provide protection of equipment from damaging
line-to-ground-fault currents by operating to cause a disconnecting
means to open all ungrounded conductors of the faulted circuit is
defined as _____.
- (210)Each
system _____ conductor, wherever accessible, shall be identified by a
separate color coding, marking tape, tagging, or other equally effective
means. This applies to multiwire branch circuits when there Is more
than one system voltage in a building.
- (220) Receptacle outlets in dwelling units are part of the ____ VA per square foot general lighting load.
- A
junction box contains two 2 inch raceways on the left side and two 2
inch raceways on the top. What is the distance between the 2 inch
raceways that contain the same conductors?
- The number of conductors permitted in a raceway is dependent on _____(3 things)
- Service
conductors only originate from the service point and terminate at the
service equipment (disconnect). Conductors supplied from back-up
generators, battery UPS systems, transformers, etc., are considered
"feeders".
- When
normally enclosed live parts are exposed for inspection or servicing,
the working space, if in a passageway or general open space, shall be
suitably _____.
- (250)
A grounding connection shall not be made to any grounded circuit
conductor on the ____ side of the service disconnecting means except as
permitted for separately derived systems or separate buildings.
- What
size square outlet box is required for: one 12/2 NM cable that
terminates on a switch, one 12/3 NM cable that terminates on a
receptacle, and the box has manufactured cable clamps.
- (240)
Type S fuses, fuse holders, and adapters are required to be designed so
that tampering and shunting would be difficult (True/False)
- (210)Dwelling
unit GFCI protection is required for all 125-volt, 15 and 20 ampere
receptacles installed to supply countertop appliances in
kitchens.(True/False)
- (240)
Unless specifically permitted in 240-3(e) through 240-3(g), the
overcurrent protection shall not exceed 15 amperes for No. 14 copper; 20
amperes for No. 12 copper; and 30 amperes for No. 10
copper.(True/False)
- The
Code prohibits damage to the internal parts of electrical equipment by
foreign material such as paint, plaster, cleaners, etc. Precautions must
be taken to provide protection from the detrimental effects of paint,
plaster, cleaners, etc. on the internal parts of ______ and ______.
- A
200 ampere feeder installed in rigid nonmetallic conduit schedule 80,
has three No. 3/0 THHN, one No. 2 THHN, and one No. 6 THHN. What size
raceway is required?
- (Article 100) Acceptable to the authority having jurisdiction means that the equipment has been _____.
- (250) Stainless steel ground rods shall not be less than _____ in diameter.
- (230) Service heads for service raceways shall be ______.
- Conductors
Added to Existing Box: How many No. 14 THHN conductors can be pulled
through a 4 x 2 ½ square box that has a plaster ring 3.6 cubic inches?
The box already contains two receptacles, five No. 12 THHN conductors,
and one No. 12 bare grounding conductor.
- A
junction box contains two 2 ½ inch raceways on the left side and one 2 ½
inch raceway on the right side. The conductors from one 2 ½ inch
raceway are pulled through the raceway on the righ wall. The other 2 ½
inch raceway conductors (on the side) are pulled through a 2 ½ inch
raceway at the bottom of the pull box. What is the distance from between
the raceways that contain the same conductors?
- (230) Service-lateral conductors are required to be insulated (except the grounded conductor) when it is _______.
- Box
Fill Requirements: One or more grounding conductors are considered ____
conductor based on the ____ grounding conductor that enters the box.
- Angle
Pull Calculation (90 degrees, diameter of raceway) must not be less
than ___ times the trade diameter of the largest raceway plus the sum of
the diameters of the remaining raceways on the same wall of the box.
- Equipment approved for use in dry locations shall be protected against permanent damage from the weather during _____.
- (250)
If none of the electrodes specified in Section 250-50 are available,
then local metal underground systems or structures (not gas); ground
rods or pipes; or plate electrodes canbe used as the required grounding
electrode.(True/False)
- Outlet Box Size: What size outlet box is required for six No. 12 THHN conductors, and three No. 12 THW conductors?
- Straight
Pull Calculation (length of raceway): The minimum distance from where
the raceway enters to the opposite wall must not be less than _____
times the trade size of the largest raceway.
- At
least one entrance not less than 24 inches wide and 6 ½ feet high shall
be provided to give access to the working space about electrical
equipment that operates at over 600 volts, nominal. On switchboard and
control panels exceeding 6 feet in width, there shall be one entrance at
each end of such equipment, except where the work space required in
Section 110.34(a) is doubled (True/False)
- Conductors larger than No. 4/0 are measured in _____.
- (210)A
single receptacle installed on an individual branch circuit must be
rated at least _____ percent of the rating of the circuit.
- A signaling circuit is any electric circuit that energizes signaling equipment. (True/False)
- (210)A branch circuit rated 20 amps serves four receptacles. The rating of the receptacles must not be less than _____ amperes.
- (240)
Conductors supplying a transformer shall be permitted to be tapped
without overcurrent protection at the tap where the conductors supplying
the _____ of the transformer have an ampacity at least 1/3 the rating
of the overcurrent device protecting the feeder conductors.
- The
temperature rating associated with the ampacity of a _____ shall be so
selected and coordinated so as to not exceed the lowest temperature
rating of any connected termination, conductor, or device.
- A
separate portion of a conduit or tubing system that provides access
through a removable cover(s) to the interior of the system at a junction
of two or more sections of the system or at a terminal point of the
system is defined as a(n)
- (210)A permanently installed cord connector on a cord pendant shall be considered a receptacle outlet.(True/False)
- In judging equipment, considerations such as mechanical strength and arcing effects should be evaluated(True/False)
- When
conductors enter an eclosure opposite a removable cover, the distance
from where the conductors enter to the removable cover determined using
Table _____ (1 terminal column)
- How many No. 1/0 XHHW can be installed in 2" flexible metal conduit?
- (240)
Single-pole breakers with approved handle ties can be used for the
protection for each ungrounded conductor for line to nuetral connected
loads.(True/False)
- (210)Indwelling units, outdoor receptacles can be connected to the 20 ampere small appliance branch circuit.(True/False)
- (250)
What size copper grounding electrode conductor is required for a
service that has three sets of 500 Kcmil copper per phase?
- The
NEC required series-related installations to be field-marked to
indicate the maximum level of fault-current for which the system has
been installed.
- (250) The grounding electrode conductor shall be made of copper, aluminum, or copper-clad aluminum.(True/False)
- A ______ location may be temporarily subject to dampness and wetness.
- A
junction box contains two 2 ½ inch raceways on the left side and one 2 ½
inch raceway on the right side. The conductors from one 2 ½ inch
raceway are pulled through the raceway on the righ wall. The other 2 ½
inch raceway conductors (on the side) are pulled through a 2 ½ inch
raceway at the bottom of the pull box. What is the distance from the
bottom wall to the top wall?
- (Article
90)Explanatory material, such as references to other standards,
references to related Sections of the Code or information related to a
Code rule is included in the NEC in the form of informational notes.
(True/False)
- (230)
There shall be no more than _____ disconnects installed for each
service, or for each set of service-entrance conductors as permitted in
Section 230-2 and 230-40.
- Number
of Conductors in an Outlet Box: Using Table 314-16a, how many No. 14
THHN conductors are permitted in a 4 x 1 ½ round box?
- Box
Fill Requirements: Fixture wires smaller than NO. 14 from a domed
fixture or similar canopy are considered as ______ conductor
- What size square box is required for 6 No. 14 THHN and 3 No. 14 THW?
- An enclosure or device so constructed that a beating rain will not enter is _______.
- (210)Receptacle and cord connectors having grounding terminals must have those terminals effectively _______.
- U-Pull
Calculations: The distance from were the raceways enter to the opposite
wall must not be less than _____ times the trade diameter of the
largest raceway plus the sum of te diameters of the remaining raceways
on the same wall.
- Circuit
protective devices are used to clear a fault without the occurrence of
extensive damage to te electrical components of the circuit. This fault
shall be assumed to be either between two or more of the _____ or
between any circuit conductor and the grounding conductor or enclosing
metal raceway.
- (230) In a multiple-occupancy building, each occupant shall have access to its own service_____.
- Working space distances shall be measured from the _____ of equipment or apparatus if such are enclosed
- A single panel or group of panel units designed for assembly in the form of a single panel is called a _______
- How many NO. 6 RHH (without outer cover) can be installed in a 1 " nonmetallic tubing?
- (230)
Where the service disconnecting means is mounted on a switchboard
having exposed busbars on the back, a raceway shall be permitted to
terminate with a _____.
- Where
switches, cutouts or other equipment operating at 600 volts nominal, or
less are installed in a room or enclosure where there are exposed live
parts or exposed wiring operating at over 600 volts, nominal, the
high-voltage equipment shall be effectively separated from the space
occupied by _____ by a suitable partition, fence, or screen.
- (250)
Currents that introduce noise or data errors in electronic equipment
shall be considered objectionable currents.(True/False)